• Shopping Cart
    There are no items in your cart

UNE-EN IEC 61326-3-2:2018

Current

Current

The latest, up-to-date edition.

Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 3-2: Immunity requirements for safety-related systems and for equipment intended to perform safety-related functions (functional safety) - Industrial applications with specified electromagnetic environment (Endorsed by Asociación Española de Normalización in January of 2019.)

Available format(s)

Hardcopy , PDF

Language(s)

English

Published date

01-01-2019

US$91.20
Excluding Tax where applicable

This part of IEC 61326 covers all equipment within the scope of IEC 61326-1, but is limited to

systems and equipment for industrial applications within a specified electromagnetic

environment and intended to perform safety functions as defined in IEC 61508 with SIL 1-3.



The electromagnetic environments encompassed by this product family standard are

industrial, both indoor and outdoor, and based on the requirements of the process industry,

specifically chemical/petrochemical/pharmaceutical manufacturing plants using the mitigation

measures given in Annex C. The difference between the electromagnetic environment

covered by this standard compared to the general industrial environment (see IEC 61326-3-1)

is due to the mitigation measures employed against electromagnetic phenomena leading to a

specified electromagnetic environment with test values that have been proven in practice.



The environment of industrial application with a specified electromagnetic environment

typically includes the following characteristics:

industrial area with limited access;

limited use of mobile transmitters;

dedicated cables for power supply and control, signal or communication lines;

separation between power supply and control, signal or communication cables;

factory building mostly consisting of metal construction;

overvoltage/lightning protection by appropriate measures (for example, metal construction of the building or use of protection devices);

pipe heating systems driven by a.c. main power;

no high-voltage substation close to sensitive areas;

presence of CISPR 11 Group 2 ISM equipment using ISM frequencies only with low power;

competent staff;

periodical maintenance of equipment and systems;

mounting and installation guidelines for equipment and systems.



Equipment and systems considered as proven-in-use according to IEC 61508 or prior use

according to IEC 61511 are excluded from the scope of IEC 61326-3-2.



Fire alarm systems and security alarm systems intended for protection of buildings are

excluded from the scope of IEC 61326-3-2.

Committee
CTN 203/SC 65
DocumentType
Standard
ISBN
978-2-8322-4213-1
Pages
48
ProductNote
THIS STANDARD ALSO REFERS TO NAMUR Recommendation NE 21:2012, NAMUR Recommendation NE 93:2003, NAMUR Recommendation NE 98:2007
PublisherName
Asociación Española de Normalización
Status
Current

Standards Relationship
EN IEC 61326-3-2:2018 Identical
IEC 61326-3-2:2017 Identical