BS EN ISO 16890-2:2016
Superseded
A superseded Standard is one, which is fully replaced by another Standard, which is a new edition of the same Standard.
View Superseded by
Air filters for general ventilation Measurement of fractional efficiency and air flow resistance
Hardcopy , PDF
09-30-2022
English
03-31-2017
Foreword
Introduction
1 Scope
2 Normative references
3 Terms and definitions
4 Symbols and abbreviated terms
5 General test requirements
6 Test materials
7 Test equipment
8 Qualification of test rig and apparatus
9 Test methods
10 Data reduction and calculations
11 Reporting results
Annex A (informative) - Example
Annex B (informative) - Resistance to air flow calculation
Bibliography
Defines the aerosol production, the test equipment and the test methods used for measuring fractional efficiency and air flow resistance of air filters for general ventilation.
Committee |
MCE/21
|
DevelopmentNote |
Supersedes 14/30268894 DC. (12/2016) Together with BS EN ISO 16890-1, BS EN ISO 16890-3 and BS EN ISO 16890-4, it supersedes DD ISO/TS 21220. Together with BS EN ISO 16890-1, BS EN ISO 16890-3 and BS EN ISO 16890-4, it supersedes BS EN 779, which remains current and will be withdrawn on 30/06/2018. (03/2017)
|
DocumentType |
Standard
|
Pages |
72
|
PublisherName |
British Standards Institution
|
Status |
Superseded
|
SupersededBy | |
Supersedes |
This part of ISO16890 specifies the aerosol production, the test equipment and the test methods used for measuring fractional efficiency and air flow resistance of air filters for general ventilation. It is intended for use in conjunction with ISO16890‑1 , ISO16890‑3 and ISO16890‑4 . The test method described in this part of ISO16890 is applicable for air flow rates between 0,25m 3/s (900m 3/h, 530ft 3/min) and 1,5m 3/s (5400m 3/h, 3178ft 3/min), referring to a test rig with a nominal face area of 610mm×610mm (24,0 inch×24,0 inch). ISO16890 (all parts) refers to particulate air filter elements for general ventilation having an ePM 1 efficiency less than or equal to 99%and an ePM 10 efficiency greater than 20%when tested as per the procedures defined within ISO16890(allparts) . NOTE The lower limit for this test procedure is set at a minimum ePM 10 efficiency of 20%since it will be very difficult for a test filter element below this level to meet the statistical validity requirements of this procedure. Air filter elements outside of this aerosol fraction are evaluated by other applicable test methods, (see ISO29463 (all parts)). Filter elements used in portable room-air cleaners are excluded from the scope. The performance results obtained in accordance with ISO16890 (all parts) cannot by themselves be quantitatively applied to predict performance in service with regard to efficiency and lifetime.
Standards | Relationship |
ISO 16890-2:2016 | Identical |
EN ISO 16890-2:2016 | Identical |
ASHRAE 52.2 : 2017 | METHOD OF TESTING GENERAL VENTILATION AIR-CLEANING DEVICES FOR REMOVAL EFFICIENCY BY PARTICLE SIZE |
ISO 2854:1976 | Statistical interpretation of data — Techniques of estimation and tests relating to means and variances |
ISO 29464:2017 | Cleaning of air and other gases — Terminology |
ISO 16890-3:2016 | Air filters for general ventilation — Part 3: Determination of the gravimetric efficiency and the air flow resistance versus the mass of test dust captured |
ISO 16890-4:2016 | Air filters for general ventilation — Part 4: Conditioning method to determine the minimum fractional test efficiency |
EN 779:2012 | Particulate air filters for general ventilation - Determination of the filtration performance |
ISO 16890-1:2016 | Air filters for general ventilation — Part 1: Technical specifications, requirements and classification system based upon particulate matter efficiency (ePM) |
ISO 14644-3:2005 | Cleanrooms and associated controlled environments Part 3: Test methods |
ISO 5167-1:2003 | Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full Part 1: General principles and requirements |
ISO 21501-4:2007 | Determination of particle size distribution Single particle light interaction methods Part 4: Light scattering airborne particle counter for clean spaces |
ISO 12103-1:2016 | Road vehicles — Test contaminants for filter evaluation — Part 1: Arizona test dust |
ISO 21501-1:2009 | Determination of particle size distribution — Single particle light interaction methods — Part 1: Light scattering aerosol spectrometer |