BS EN 50281-2-1:1999
Current
The latest, up-to-date edition.
Electrical apparatus for use in the presence of combustible dust. Test methods Methods of determining minimum ignition temperatures
Hardcopy , PDF
English
05-15-1999
Specifies two test methods for determining the minimum ignition temperatures of dust for the purpose of selecting apparatus for use in presence of combustible dusts.
Committee |
EXL/31
|
DevelopmentNote |
Supersedes 82/24413 DC. (09/2005)
|
DocumentType |
Standard
|
Pages |
28
|
PublisherName |
British Standards Institution
|
Status |
Current
|
This European Standard specifies two test methods for determining the minimum ignition temperatures of dust for the purpose of selecting electrical apparatus for use in the presence of combustible dust in accordance with EN 50281-1-2:1998 and constructed in accordance with EN 50281-1-1:1998.
These methods are not suitable for use with substances having explosive properties.
Method A (clause 4) is applicable to the determination of the minimum temperature of a prescribed hot surface which will result in the decomposition and/or ignition of a layer of dust of a specified thickness deposited on it. The method is particularly relevant to industrial equipment with which dusts are present on hot surfaces in thin layers exposed to the atmosphere.
Method B (clause 5) is applicable to the determination of the minimum temperature of a prescribed hot surface which will result in the ignition of a cloud of given sample of dust or other particulate solid. The test is intended to be carried out as a complementary test after determining the minimum ignition temperature of a dust layer by method A of this European Standard.
NOTE 1 Concerning method B: because the method of operation of the furnace gives short residence times for dust particles within it, this method of test is applicable to industrial equipment where dust is present as a cloud for a short time. This method of test is of small scale and the results are not necessarily representative of all industrial conditions.
NOTE 2 Concerning method B: the method is not applicable to dusts which may, over a longer period of time than provided for in the test method, produce gasses from deposits generated during pyrolysis or smouldering.
Standards | Relationship |
UNE-EN 50281-2-1:1999 | Identical |
NF EN 50281-2-1 : 2000 | Identical |
I.S. EN 50281-2-1:1999 | Identical |
DIN EN 50281-2-1 : 1999 | Identical |
NEN EN 50281-2-1 : 1998 C1 1999 | Identical |
EN 50281-2-1 : 98 COR 99 | Identical |
SN EN 50281-2-1 : 1998 | Identical |
BS 5908-2:2012 | Fire and explosion precautions at premises handling flammable gases, liquids and dusts Guide to applicable standards and regulations |
BS 7671(2008) : 2018 | REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - IET WIRING REGULATIONS |
EI SAFE HANDLING STORAGE BIOMASS TPS : 1ED 2016 | SAFE HANDLING AND STORAGE OF BIOMASS IN THERMAL POWER STATIONS |
12/30258581 DC : 0 | BS 5908-2 - FIRE AND EXPLOSION PRECAUTIONS AT PREMISES HANDLING FLAMMABLE GASES, LIQUIDS AND DUSTS - PART 2: GUIDE TO APPLICABLE STANDARDS AND REGULATIONS |
BS 7671(2008) : 2008 | REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - IET WIRING REGULATIONS |
EN 50281-1-2 : 98 AMD 1 2002 | ELECTRICAL APPARATUS FOR USE IN THE PRESENCE OF COMBUSTIBLE DUST - PART 1-2: ELECTRICAL APPARATUS PROTECTED BY ENCLOSURES - SELECTION, INSTALLATION AND MAINTENANCE |
EN 50281-1-1 : 98 AMD 1 2002 | ELECTRICAL APPARATUS PROTECTED BY ENCLOSURES - CONSTRUCTION AND TESTING FOR USE IN THE PRESENCE OF COMBUSTIBLE DUST - ELECTRICAL APPARATUS PROTECTED BY ENCLOSURES - CONSTRUCTION AND TESTING |
ISO 4225:1994 | Air quality General aspects Vocabulary |
ISO 565:1990 | Test sieves — Metal wire cloth, perforated metal plate and electroformed sheet — Nominal sizes of openings |
Access your standards online with a subscription
Features
-
Simple online access to standards, technical information and regulations.
-
Critical updates of standards and customisable alerts and notifications.
-
Multi-user online standards collection: secure, flexible and cost effective.