Foreword
1 Scope
2 Normative references
3 Terms and definitions
4 Rated voltage
5 Conductors
6 Insulation
7 Identification of cores
8 Laying-up
9 Bedding
10 Armour
11 Oversheath
12 Cable marking and additional
information
13 End sealing
14 Schedule of tests
15 Test conditions
16 Routine tests
17 Sample tests
18 Type tests
Annexes
Annex A (informative) - Guide to use and installation
of cables
Annex B (normative) - Armour wire tests
Annex C (normative) - Compatibility test
Annex D (normative) - Abrasion resistance test
Annex E (normative) - Insulation resistance constant test
on oversheath
Annex F (normative) - Resistance of conductor and
armour
Annex G (informative) - Gross cross-sectional area
of armour
Annex H (normative) - Test for shrinkage of oversheath
on cable
Annex I (informative) - Guidance on type tests
Annex J (informative) - United Kingdom reference
codes
Bibliography
Describes requirements for the construction and performance of thermosetting insulated, armoured cables of rated voltages of 600/1000 V and 1900/3300 V, having low emission of smoke and corrosive gases when affected by fire.
Committee |
GEL/20
|
DevelopmentNote |
Supersedes BS 6724(1997) which remains current and will be withdrawn on 30.04.2017. Supersedes 15/30301443 DC. (05/2016)
|
DocumentType |
Standard
|
Pages |
50
|
PublisherName |
British Standards Institution
|
Status |
Current
|
Supersedes |
This British Standard specifies requirements for the construction and performance of thermosetting insulated, armoured cables of rated voltages of 600/1000V and 1900/3300V, having low emission of smoke and corrosive gases when affected by fire. NOTE1 Other thermosetting insulated, armoured cables for voltages of 600/1000V and 1900/3300V can be found in BS5467 , but these do not have low levels of emission of smoke and corrosive products under exposure to fire. This British Standard is applicable to cables for use in fixed installations in industrial areas, buildings or similar applications. This British Standard specifies requirements for the following types of cables: 600/1000V cables, wire armoured and oversheathed having single-core, two-, three-, four- and five-core stranded copper conductor; 600/1000V multicore auxiliary cables, wire armoured, and oversheathed, stranded copper conductor; and 1900/3300V cables, wire armoured and oversheathed, having single-core or three-core stranded copper conductor. This British Standard is applicable to cables that are designed for a maximum sustained conductor temperature of 90°C and for a maximum short-circuit conductor temperature of 250°C (for a maximum of 5s). NOTE2 Limitation on the temperature of the cables may be imposed in situations where they might be touched or where they could touch other materials. NOTE3 AnnexA gives a guide to the use and installation of cables, AnnexB gives armour wire tests, AnnexC gives a compatibility test, AnnexD gives an abrasion resistance test, AnnexE gives an insulation resistance constant test on oversheath, AnnexF gives the resistance of conductor and armour, AnnexG gives the gross cross-sectional area of armour, AnnexH gives a test for shrinkage of oversheath on cable, AnnexI gives guidance on type tests and AnnexJ gives the standard United Kingdom reference codes.
BS EN 62444:2013 | Cable glands for electrical installations |
BS EN 60811-401:2012 | Electric and optical fibre cables. Test methods for non-metallic materials Miscellaneous tests. Thermal ageing methods. Ageing in an air oven |
BS EN 61034-2 : 2005 | MEASUREMENT OF SMOKE DENSITY OF CABLES BURNING UNDER DEFINED CONDITIONS PART 2: TEST PROCEDURE AND REQUIREMENTS |
BS EN 60229:2008 | Electric cables. Tests on extruded oversheaths with a special protective function |
BS EN 50262:1999 | Cable glands for electrical installations |
BS EN 60811-502:2012 | Electric and optical fibre cables. Test methods for non-metallic materials Mechanical tests. Shrinkage test for insulations |
BS EN 61914:2016 | Cable cleats for electrical installations |
BS EN 60332-1-2 : 2004 | TESTS ON ELECTRIC AND OPTICAL FIBRE CABLES UNDER FIRE CONDITIONS - PART 1-2: TEST FOR VERTICAL FLAME PROPAGATION FOR A SINGLE INSULATED WIRE OR CABLE - PROCEDURE FOR 1 KW PRE-MIXED FLAME (IEC 60332-1-2:2004) |
BS EN 50393:2015 | Test methods and requirements for accessories for use on distribution cables of rated voltage 0,6/1,0 (1,2) kV |
BS EN 60228:2005 | Conductors of insulated cables |
BS 7671(2008) : 2008 | REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - IET WIRING REGULATIONS |
BS 8573:2012 | Electric cables. Thermosetting insulated, non-armoured cables with a voltage of 600/1 000V, for fixed installations, having low emissions of smoke and corrosive gases when affected by fire |
BS EN 60332-3-24:2009 | Tests on electric and optical fibre cables under fire conditions Test for vertical flame spread of vertically-mounted bunched wires or cables. Category C |
BS EN 10244-2:2009 | Steel wire and wire products. Non-ferrous metallic coatings on steel wire Zinc or zinc alloy coatings |
BS EN 62275:2015 | Cable management systems. Cable ties for electrical installations |
BS EN 60079-14:2014 | Explosive atmospheres Electrical installations design, selection and erection |
BS EN 60811-501 : 2012 | ELECTRIC AND OPTICAL FIBRE CABLES - TEST METHODS FOR NON-METALLIC MATERIALS - PART 501: MECHANICAL TESTS - TESTS FOR DETERMINING THE MECHANICAL PROPERTIES OF INSULATING AND SHEATHING COMPOUNDS |
BS 5467:2016 | Electric cables. Thermosetting insulated, armoured cables of rated voltages of 600/1 000 V and 1 900/3 300 V for fixed installations. Specification |
IEC 60183:2015 | Guidance for the selection of high-voltage A.C. cable systems |
BS EN 50395 : 2005 | ELECTRICAL TEST METHODS FOR LOW VOLTAGE ENERGY CABLES |
BS EN ISO 6892-1:2016 | Metallic materials. Tensile testing Method of test at room temperature |
BS EN 62230 : 2007 | ELECTRIC CABLES - SPARK-TEST METHOD |
IEC 60050-461:2008 | International Electrotechnical Vocabulary (IEV) - Part 461: Electric cables |
BS EN 50363-5 : 2005 | INSULATING, SHEATHING AND COVERING MATERIALS FOR LOW VOLTAGE ENERGY CABLES - PART 5: HALOGEN-FREE, CROSS-LINKED INSULATING COMPOUNDS |
BS EN 50396 : 2005 | NON ELECTRICAL TEST METHODS FOR LOW VOLTAGE ENERGY CABLES |
BS EN 60754-1:2014 | Test on gases evolved during combustion of materials from cables Determination of the halogen acid gas content |
BS 8512:2008 | Electric cables. Code of practice for the storage, handling, installation and disposal of cables on wooden drums |