BS EN 62271-105:2012

Superseded

Superseded

A superseded Standard is one, which is fully replaced by another Standard, which is a new edition of the same Standard.

View Superseded by

High-voltage switchgear and controlgear Alternating current switch-fuse combinations for rated voltages above 1 kV up to and including 52 kV

Available format(s)

Hardcopy , PDF

Superseded date

20-11-2023

Superseded by

BS EN IEC 62271-105:2023

Language(s)

English

Published date

31-01-2013

£276.00
Excluding VAT

1 General
2 Normal and special service conditions
3 Terms and definitions
4 Ratings
5 Design and construction
6 Type tests
7 Routine tests
8 Guide for the selection of switch-fuse combinations
9 Information to be given with enquiries, tenders
   and orders
10 Transport, storage, installation, operation
   and maintenance
11 Safety
12 Influence of the product on the environment
Annex A (informative) - Example of the coordination
        of fuses, switch and transformer
Annex B (normative) - Procedure for determining
        transfer current
Annex C (normative) - Tolerances on test quantities
        for type tests
Bibliography

Pertains to three-pole units for public and industrial distribution systems which are functional assemblies of switches including switch-disconnectors and current-limiting fuses designed so as to be capable of - breaking, at the rated recovery voltage, any current up to and including the rated short-circuit breaking current; - making, at the rated voltage, circuits to which the rated short-circuit breaking current applies.

Committee
PEL/17
DevelopmentNote
Supersedes BS EN 60420 Supersedes 99/200375 DC (09/2004) Supersedes 10/30218329 DC. (01/2013)
DocumentType
Standard
Pages
56
PublisherName
British Standards Institution
Status
Superseded
SupersededBy
Supersedes

Subclause 1.1 of IEC 62271-1:2007 is not applicable, and is replaced as follows:.

This part of IEC 62271 applies to three-pole units for public and industrial distribution systems which are functional assemblies of switches including switch-disconnectors and current-limiting fuses designed so as to be capable of

  • breaking, at the rated recovery voltage, any current up to and including the rated short-circuit breaking current;

  • making, at the rated voltage, circuits to which the rated short-circuit breaking current applies.

It does not apply to fuse-circuit-breakers, fuse-contactors, combinations for motor-circuits or to combinations incorporating single capacitor bank switches.

In this standard, the word “combination” is used for a combination in which the components constitute a functional assembly. Each association of a given type of switch and a given type of fuse defines one type of combination.

In practice, different types of fuses may be combined with one type of switch, which give several combinations with different characteristics, in particular concerning the rated currents. Moreover, for maintenance purposes, the user should know the types of fuses that can be combined to a given switch without impairing compliance to the standard, and the corresponding characteristics of the so-made combination.

A switch-fuse combination is then defined by its type designation and a list of selected fuses is defined by the manufacturer, the so-called “reference list of fuses”. Compliance with this standard of a given combination means that every combination using one of the selected fuses is proven to be in compliance with this standard.

The fuses are incorporated in order to extend the short-circuit breaking rating of the combination beyond that of the switch alone. They are fitted with strikers in order both to open automatically all three poles of the switch on the operation of a fuse and to achieve a correct operation at values of fault current above the minimum melting current but below the minimum breaking current of the fuses. In addition to the fuse strikers, the combination may be fitted with either an over-current release or a shunt release.

NOTE In this standard the term “fuse” is used to designate either the fuse or the fuse-link where the general meaning of the text does not result in ambiguity.

This standard applies to combinations designed with rated voltages above 1 kV up to and including 52 kV for use on three-phase alternating current systems of either 50 Hz or 60 Hz.

Fuses are covered by IEC 60282-1.

Devices that require dependent manual operation are not covered by this standard.

Switches, including their specific mechanism, shall be in accordance with IEC 62271-103 except for the short-time current and short-circuit making requirements where the currentlimiting effects of the fuses are taken into account.

Earthing switches forming an integral part of a combination are covered by IEC 62271-102.

IEC 62271-100:2008+AMD1:2012+AMD2:2017 CSV High-voltage switchgear and controlgear - Part 100: Alternating-current circuit-breakers
IEC TR 60787:2007 Application guide for the selection of high-voltage current- limiting fuse-links for transformer circuits
IEC 62271-202:2014 High-voltage switchgear and controlgear - Part 202: High-voltage/ low-voltage prefabricated substation
EN 62271-1:2017 High-voltage switchgear and controlgear - Part 1: Common specifications for alternating current switchgear and controlgear
EN 62271-102:2002/AC:2014 HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR - PART 102: ALTERNATING CURRENT DISCONNECTORS AND EARTHING SWITCHES (IEC 62271-102:2001/A2:2013)
IEC 60282-1:2009+AMD1:2014 CSV High-voltage fuses - Part 1: Current-limiting fuses
EN 62271-103:2011 High-voltage switchgear and controlgear - Part 103: Switches for rated voltages above 1 kV up to and including 52 kV
IEC 62271-103:2011 High-voltage switchgear and controlgear - Part 103: Switches for rated voltages above 1 kV up to and including 52 kV
IEC 62271-1:2017 High-voltage switchgear and controlgear - Part 1: Common specifications for alternating current switchgear and controlgear
EN 60282-1:2009/A1:2014 HIGH-VOLTAGE FUSES - PART 1: CURRENT-LIMITING FUSES (IEC 60282-1:2009)
IEC 62271-107:2012 High-voltage switchgear and controlgear - Part 107: Alternating current fused circuit-switchers for rated voltages above 1 kV up to and including 52 kV
IEC 62271-102:2001+AMD1:2011+AMD2:2013 CSV High-voltage switchgear and controlgear - Part 102: Alternatingcurrent disconnectors and earthing switches

Access your standards online with a subscription

Features

  • Simple online access to standards, technical information and regulations.

  • Critical updates of standards and customisable alerts and notifications.

  • Multi-user online standards collection: secure, flexible and cost effective.