FOREWORD
INTRODUCTION
1 Scope
2 Normative references
3 Terms and definitions
4 Ratings
5 Operating conditions
6 Ordering information and markings
7 Test requirements
8 Type tests
9 Routine tests
10 Requirements and tests for non-capacitance graded
bushings of rated highest voltages for equipment up
to and including 52 kV
11 Recommendations for transport, storage, erection,
operation and maintenance
12 Safety
13 Environmental aspects
Annex A (informative) - Determination of the hottest
spot in bushings with conductors embedded in
the insulation material
Bibliography
IEC 60137:2017 RLV contains both the official IEC International Standard and its Redline version. The Redline version is available in English only and provides you with a quick and easy way to compare all the changes between the official IEC Standard and its previous edition.
IEC 60137:2017 specifies the characteristics and tests for insulated bushings.
This standard is applicable to bushings, as defined in Clause 3, intended for use in electrical apparatus, machinery, transformers, switchgear and installations for three-phase alternating current systems, having highest voltage for equipment above 1 000 V and power frequencies of 15 Hz up to and including 60 Hz.
Subject to special agreement between purchaser and supplier, this standard may be applied, in part or as a whole, to the following:
- bushings used in other than three-phase systems;
- bushings for high-voltage direct current systems;
- bushings for testing transformers;
- bushings for capacitors.
Special requirements and tests for transformer bushings in this standard apply also to reactor bushings.
This standard is applicable to bushings made and sold separately. Bushings which are a part of an apparatus and which cannot be tested according to this standard should be tested with the apparatus of which they form part. This edition includes the following significant technical changes with respect to the previous edition:
- Resin-impregnated synthetic (RIS) bushings has been introduced.
- Bushings with Um ≤ 1,1 kV, Um = 1100 kV and Um = 1200 kV have been introduced.
- Temperature rise testing has been included for liquid-insulated bushings according to clause to 3.4.
- Introducing dry lightning impulse testing as a routine test for all transformer bushings with Um > 72,5 kV.
- The altitude correction procedure has been revised ( > 1 000 m).
- An explanation about Very Fast Transient (VFT) phenomenon and its impact on bushings has been included.
The contents of the corrigendum of May 2018 have been included in this copy.
Committee |
TC 36/SC 36A
|
DevelopmentNote |
Stability Date: 2019. (06/2017)
|
DocumentType |
Redline
|
Pages |
188
|
PublisherName |
International Electrotechnical Committee
|
Status |
Current
|
Supersedes |
IEC GUIDE 109:2012 | Environmental aspects - Inclusion in electrotechnical product standards |
IEC 60480:2004 | Guidelines for the checking and treatment of sulfur hexafluoride (SF<sub>6</sub>) taken from electrical equipment and specification for its re-use |
IEC 60038:2009 | IEC standard voltages |
IEC 60270:2000+AMD1:2015 CSV | High-voltage test techniques - Partial discharge measurements |
IEC 60076-7:2005 | Power transformers - Part 7: Loading guide for oil-immersed power transformers |
IEC 62155:2003 | Hollow pressurized and unpressurized ceramic and glass insulators for use in electrical equipment with rated voltages greater than 1 000 V |
IEC 60050-471:2007 | International Electrotechnical Vocabulary (IEV) - Part 471: Insulators |
IEC 62217:2012 | Polymeric HV insulators for indoor and outdoor use - General definitions, test methods and acceptance criteria |
IEC 60422:2013 | Mineral insulating oils in electrical equipment - Supervision and maintenance guidance |
IEC TS 60815-2:2008 | Selection and dimensioning of high-voltage insulators intended for use in polluted conditions - Part 2: Ceramic and glass insulators for a.c. systems |
IEC 60050-212:2010 | International Electrotechnical Vocabulary (IEV) - Part 212: Electrical insulating solids, liquids and gases |
IEC 60076-5:2006 | Power transformers - Part 5: Ability to withstand short circuit |
IEC 60376:2005 | Specification of technical grade sulfur hexafluoride (SF<sub>6</sub>) for use in electrical equipment |
IEC 60216-2:2005 | Electrical insulating materials - Thermal endurance properties - Part 2: Determination of thermal endurance properties of electrical insulating materials - Choice of test criteria |
IEC 61099:2010 | Insulating liquids - Specifications for unused synthetic organic esters for electrical purposes |
IEC 60505:2011 | Evaluation and qualification of electrical insulation systems |
IEC 60836:2015 | Specifications for unused silicone insulating liquids for electrotechnical purposes |
IEC 60296:2012 RLV | Fluids for electrotechnical applications - Unused mineral insulating oils for transformers and switchgear |
IEC 60076-3:2013 | Power transformers - Part 3: Insulation levels, dielectric tests and external clearances in air |
IEC 60050-421:1990 | International Electrotechnical Vocabulary (IEV) - Part 421: Power transformers and reactors |
IEC 61462:2007 | Composite hollow insulators - Pressurized and unpressurized insulators for use in electrical equipment with rated voltage greater than 1 000 V - Definitions, test methods, acceptance criteria and design recommendations |
IEC 60068-2-17:1994 | Basic environmental testing procedures - Part 2-17: Tests - Test Q: Sealing |
IEC 60076-1:2011 | Power transformers - Part 1: General |
IEC 62271-203:2011 | High-voltage switchgear and controlgear - Part 203: Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV |
IEC TR 60943:1998+AMD1:2008 CSV | Guidance concerning the permissible temperature rise for parts of electrical equipment, in particular for terminals |
IEC GUIDE 111:2004 | Electrical high-voltage equipment in high-voltage substations - Common recommendations for product standards |
IEC 60867:1993 | Insulating liquids - Specifications for unused liquids based on synthetic aromatic hydrocarbons |
IEC 62271-1:2017 | High-voltage switchgear and controlgear - Part 1: Common specifications for alternating current switchgear and controlgear |
IEC 60076-2:2011 | Power transformers - Part 2: Temperature rise for liquid-immersed transformers |
IEC 60059:1999+AMD1:2009 CSV | IEC standard current ratings |
IEC 60060-1:2010 | High-voltage test techniques - Part 1: General definitions and test requirements |
IEC 60507:2013 | Artificial pollution tests on high-voltage ceramic and glass insulators to be used on a.c. systems |
IEC 60071-1:2006+AMD1:2010 CSV | Insulation co-ordination - Part 1: Definitions, principles and rules |
IEC TS 60815-1:2008 | Selection and dimensioning of high-voltage insulators intended for use in polluted conditions - Part 1: Definitions, information and general principles |
IEC TS 60815-3:2008 | Selection and dimensioning of high-voltage insulators intended for use in polluted conditions - Part 3: Polymer insulators for a.c. systems |
IEC TS 61463:2016 | Bushings - Seismic qualification |
Access your standards online with a subscription
Features
-
Simple online access to standards, technical information and regulations.
-
Critical updates of standards and customisable alerts and notifications.
-
Multi-user online standards collection: secure, flexible and cost effective.