BS EN 60255-26:2013
Current
The latest, up-to-date edition.
Measuring relays and protection equipment Electromagnetic compatibility requirements
Hardcopy , PDF
English
31-07-2014
Committee |
PEL/95
|
DevelopmentNote |
Supersedes BS EN 50263 and 00/203618 DC (02/2005) Supersedes 07/30163348 DC. (09/2010) Supersedes BS EN 60255-11, BS EN 60255-22-1, BS EN 60255-22-2, BS EN 60255-22-3, BS EN 60255-22-4, BS EN 60255-22-5, BS EN 60255-22-6, BS EN 60255-22-7, BS EN 60255-25 & 10/30240055 DC. (08/2014)
|
DocumentType |
Standard
|
Pages |
52
|
PublisherName |
British Standards Institution
|
Status |
Current
|
Supersedes |
|
IEC 60255-26:2013 is applicable to measuring relays and protection equipment, taking into account combinations of devices to form schemes for power system protection including the control, monitoring, communication and process interface equipment used with those systems. This standard specifies the requirements for electromagnetic compatibility for measuring relays and protection equipment. The requirements specified in this standard are applicable to measuring relays and protection equipment in a new condition and all tests specified are type tests only. This new edition includes the following significant technical changes with respect to the previous edition:
- definition of test specifications, test procedures and acceptance criteria per phenomena and port under test in one document;
- extension of radiated emission measurement for frequencies above 1 GHz;
- limitation of radiated emission measurement at 3 m distance for small equipment only;
- addition of zone A and zone B test level on surge test;
- extension of tests on the auxiliary power supply port by a.c. and d.c. voltage dips, a.c. component in d.c. (ripple) and gradual shut-down/start-up;
- harmonization of acceptance criteria for immunity tests.
Standards | Relationship |
NBN EN 60255-26 : 2013 | Identical |
NF EN 60255-26 : 2014 | Identical |
EN 60255-26:2013 | Identical |
DIN EN 60255-26 : 2014 COR 2 2015 | Identical |
IEC 60255-26:2013 | Identical |
I.S. EN 60255-26:2013 | Identical |
EN 60255-26:2013/AC:2013 | Identical |
UNE-EN 60255-26:2010 | Identical |
EN 61000-4-11:2004/A1:2017 | ELECTROMAGNETIC COMPATIBILITY (EMC) - PART 4-11: TESTING AND MEASUREMENT TECHNIQUES - VOLTAGE DIPS, SHORT INTERRUPTIONS AND VOLTAGE VARIATIONS IMMUNITY TESTS (IEC 61000-4-11:2004/A1:2017) |
IEC 61000-4-11:2004+AMD1:2017 CSV | Electromagnetic compatibility (EMC) - Part 4-11: Testing and measurement techniques - Voltage dips, short interruptions and voltage variations immunity tests |
IEC 61000-4-8:2009 | Electromagnetic compatibility (EMC) - Part 4-8: Testing and measurement techniques - Power frequency magnetic field immunity test |
IEC 61000-4-4:2012 RLV | Electromagnetic compatibility (EMC) - Part 4-4: Testing and measurement techniques - Electrical fast transient/burst immunity test |
2004/108/EC : 2004 | DIRECTIVE 2004/108/EC OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL OF 15 DECEMBER 2004 ON THE APPROXIMATION OF THE LAWS OF THE MEMBER STATES RELATING TO ELECTROMAGNETIC COMPATIBILITY AND REPEALING DIRECTIVE 89/336/EC |
IEC 61000-4-17:1999+AMD1:2001+AMD2:2008 CSV | Electromagnetic compatibility (EMC) - Part 4-17: Testing and measurement techniques - Ripple on d.c. input power port immunity test |
EN 61000-4-2:2009 | Electromagnetic compatibility (EMC) - Part 4-2: Testing and measurement techniques - Electrostatic discharge immunity test |
IEC 61000-4-6:2013 | Electromagnetic compatibility (EMC) - Part 4-6: Testing and measurement techniques - Immunity to conducted disturbances, induced by radio-frequency fields |
CISPR 22:2008 | Information technology equipment - Radio disturbance characteristics - Limits and methods of measurement |
EN 61000-4-3 : 2006 AMD 2 2010 | ELECTROMAGNETIC COMPATIBILITY (EMC) - PART 4-3: TESTING AND MEASUREMENT TECHNIQUES - RADIATED, RADIO-FREQUENCY, ELECTROMAGNETIC FIELD IMMUNITY TEST |
EN 60255-1:2010 | Measuring relays and protection equipment - Part 1: Common requirements |
EN 55022:2010/AC:2011 | INFORMATION TECHNOLOGY EQUIPMENT - RADIO DISTURBANCE CHARACTERISTICS - LIMITS AND METHODS OF MEASUREMENT (CISPR 22:2008) |
IEC TS 61000-6-5:2001 | Electromagnetic compatibility (EMC) - Part 6-5: Generic standards - Immunity for power station and substation environments |
EN 61000-4-8:2010 | Electromagnetic compatibility (EMC) - Part 4-8: Testing and measurement techniques - Power frequency magnetic field immunity test |
IEC 61000-4-2:2008 | Electromagnetic compatibility (EMC) - Part 4-2: Testing and measurement techniques - Electrostatic discharge immunity test |
IEC 61000-4-3:2006+AMD1:2007+AMD2:2010 CSV | Electromagnetic compatibility (EMC) - Part 4-3: Testing and measurement techniques - Radiated, radio-frequency, electromagnetic field immunity test |
IEC 60255-1:1967 | Electrical relays - Part 1: Instantaneous all-or-nothing relays |
EN 61000-4-4:2012 | ELECTROMAGNETIC COMPATIBILITY (EMC) - PART 4-4: TESTING AND MEASUREMENT TECHNIQUES - ELECTRICAL FAST TRANSIENT/BURST IMMUNITY TEST (IEC 61000-4-4:2012) |
CISPR 11:2015 RLV | Industrial, scientific and medical equipment - Radio-frequency disturbance characteristics - Limits and methods of measurement |
EN 61000-4-6:2014/AC:2015 | ELECTROMAGNETIC COMPATIBILITY (EMC) - PART 4-6: TESTING AND MEASUREMENT TECHNIQUES - IMMUNITY TO CONDUCTED DISTURBANCES, INDUCED BY RADIO-FREQUENCY FIELDS (IEC 61000-4-6:2013) |
EN 61000-4-16:2016 | Electromagnetic compatibility (EMC) - Part 4-16: Testing and measurement techniques - Test for immunity to conducted, common mode disturbances in the frequency range 0 Hz to 150 kHz |
IEC 61000-4-29:2000 | Electromagnetic compatibility (EMC) - Part 4-29: Testing and measurement techniques - Voltage dips, short interruptions and voltage variations on d.c. input power port immunity tests |
EN 61000-4-17:1999/A2:2009 | ELECTROMAGNETIC COMPATIBILITY (EMC) - PART 4-17: TESTING AND MEASUREMENT TECHNIQUES - RIPPLE ON D.C. INPUT POWER PORT IMMUNITY TEST |
IEC 61000-4-18:2006+AMD1:2010 CSV | Electromagnetic compatibility (EMC) - Part 4-18: Testing and measurement techniques - Damped oscillatory wave immunity test |
EN 61000-4-29:2000 | Electromagnetic compatibility (EMC) - Part 4-29: Testing and measurement techniques - Voltage dips, short interruptions and voltage variations on d.c. input power port immunity tests |