ASTM E 2652 : 2016

Superseded

Superseded

A superseded Standard is one, which is fully replaced by another Standard, which is a new edition of the same Standard.

View Superseded by

Standard Test Method for Behavior of Materials in a Tube Furnace with a Cone-shaped Airflow Stabilizer, at 750°C

Available format(s)

Hardcopy , PDF

Superseded date

14-01-2019

Superseded by

ASTM E 2652 : 2018

Language(s)

English

Published date

01-01-2016

£63.73
Excluding VAT

Committee
E 05
DocumentType
Test Method
Pages
13
PublisherName
American Society for Testing and Materials
Status
Superseded
SupersededBy
Supersedes

1.1This fire-test-response test method covers the determination under specified laboratory conditions of combustion characteristics of building materials.

1.2Limitations of this fire-test response test method are shown below.

1.2.1This test method does not apply to laminated or coated materials.

1.2.2This test method is not suitable or satisfactory for materials that soften, flow, melt, intumesce or otherwise separate from the measuring thermocouple.

1.2.3This test method does not provide a measure of an intrinsic property.

1.2.4This test method does not provide a quantitative measure of heat generation or combustibility; it simply serves as a test method with selected (end point) measures of combustibility.

1.2.5This test method does not measure the self-heating tendencies of materials.

1.2.6In this test method materials are not being tested in the nature and form used in building aplications. The test specimen consists of a small, specified volume that is either (1) cut from a thick sheet; (2) assembled from multiple thicknesses of thin sheets; or (3) placed in a container if composed of grarnular powder or loose fiber materials.

1.2.7Results from this test method apply to the specific test apparatus and test conditions and are likely to vary when changes are made to one or more of the following: (1) the size, shape, and arrangement of the specimen; (2) the distribution of organice content; (3) the exposure temperature; (4) the air supply; (5) the location of thermocouples.

1.3This test method references notes and footnotes that provide explanatory information. These notes and footnotes, excluding those in tables and figures, shall not be considered as requirements of this test method.

1.4The values stated in SI units are to be regarded as standard. The values given in parentheses are for information only.

1.5This test method is technically equivalent to ISO 1182 (see also Annex A2 and 6.4.5).

1.6This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire-hazard or fire-risk assessment of the materials, products, or assemblies under actual fire conditions.

1.7FIre testing is inherently hazardous. Adequate safeguards for personnel and property shall be employed in conducting these tests.

1.8This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

ASTM E 176 : 2018 : REV A Standard Terminology of Fire Standards
ASTM C 1696 : 2016 Standard Guide for Industrial Thermal Insulation Systems
ASTM E 136 : 2019 Standard Test Method for Assessing Combustibility of Materials Using a Vertical Tube Furnace at 750°C
NFPA 13 : 2022 Standard for the Installation of Sprinkler Systems, 2022 and 2019 Editions

Access your standards online with a subscription

Features

  • Simple online access to standards, technical information and regulations.

  • Critical updates of standards and customisable alerts and notifications.

  • Multi-user online standards collection: secure, flexible and cost effective.