Electricity metering - Electronic watthour meters (Classes 0.2 S and 0.5 S)
Hardcopy , PDF 1 User , PDF 3 Users , PDF 5 Users , PDF 9 Users
30-06-2017
English
01-01-1993
Specifies requirements for electronic watthour meters of accuracy classes 0.2 S and 0.5 S suitable for installation indoors. This Standard is technically identical with and reproduced from IEC 687:1992.
Committee |
EL-011
|
DocumentType |
Standard
|
ISBN |
0 7262 8223 5
|
Pages |
34
|
PublisherName |
Standards Australia
|
Status |
Superseded
|
SupersededBy | |
Supersedes | |
UnderRevision |
This International Standard applies only to newly manufactured static watt-hour meters of accuracy classes 0,2 S and 0,5 S, for the measurement of alternating-current electrical active energy of a frequency in the range 45 Hz to 65 Hz and to their type tests only.It applies only to transformer-operated static meters for indoor application consisting of one or more measuring elements and registers enclosed together in the same case.NOTE - IEC 185 describes transformers having a measuring range of 0,05In to 1,2In, or of 0,05In to 1,5In,or of 0,05In to 2In and transformers having a measuring range of 0,01In to 1,2In for accuracy classes 0,2 Sand 0,5 S. As the measuring ranges of a meter and its associated transformers have to be matched and as only transformers of classes 0,2 S and 0,5 S have the accuracy required to operate the meters of this standard, the measuring range of the meter will be 0,01In to 1,2In.It also applies to operationindicators, test outputs and meters which measure energy in both directions.This standard does not apply to:a) watt-hour meters where the voltage across the connection terminals exceeds 600 V (line-to-line voltage for meters for polyphase systems);b) portable meters and meters for outdoor use;c) data interfaces to the register of the meter;d) reference meters.Where the display and/or the memory(ies) is/are external or where other elements are enclosed in the meter case (such as maximum demand indicators, telemetering, time switches or remote control, etc.) this standard applies only to the metering section.This standard does not cover the acceptance tests and the conformity tests (both testing procedures are connected with legal requirements of the different countries and could only be taken care of partially).For rack-mounted meters, the mechanical properties are not covered in this standard.
Standards | Relationship |
IEC 60687:1992 | Identical |
First published as AS 1284.9-1993.
AS 1099.2KA-1978 | Basic environmental testing procedures for electrotechnology Tests - Test Ka - Salt mist |
AS 1939-1990 | Degrees of protection provided by enclosures for electrical equipment (IP Code) |
AS 2420-1987 | Fire test methods for solid insulating materials and non-metallic enclosures used in electrical equipment |
AS 1099.2AD-1980 | Basic environmental testing procedures for electrotechnology Tests - Test Ad - Cold test for heat-dissipating specimens with gradual change of temperature |
AS 1099.2DB-1982 | Basic environmental testing procedures for electrotechnology Tests - Test Db - Damp heat, cyclic (12 + 12 hours) |
AS 1284.5-1992 | Electricity metering General purpose electronic watthour meters |
AS 2926-1987 | Standard voltages - Alternating (50 Hz) and direct |
AS 1104-1978 | Informative symbols for use on electrical and electronic equipment |
AS 2768-1985 | Electrical insulating materials - Evaluation and classification based on thermal endurance |
AS/NZS 1044:1995 | Limits and methods of measurement of radio disturbance characteristics of electrical motor-operated and thermal appliances for household and similar purposes, electric tools and similar electric apparatus |
AS 1099.2.6-1988 | Basic environmental testing procedures for electrotechnology Tests - Test Fc - Vibration (sinusoidal) |
AS 1675-1986 | Current transformers - Measurement and protection |
AS 1099.2.27-1988 | Basic environmental testing procedures for electrotechnology Tests - Test Ea - Shock |
AS 1099.2BD-1980 | Basic environmental testing procedures for electrotechnology Tests - Test Bd - Dry heat test for heat-dissipating specimens with gradual change of temperature |
AS 1931.1-1996 | High-voltage test techniques - General definitions and test requirements |
AS 1931.2-1996 | High-voltage test techniques - Measuring systems |
AS 1243-1982 | Voltage transformers for measurement and protection |
AS/NZS 1284.13:2002 | Electricity metering In-service compliance testing (Reconfirmed 2016) |
Access your standards online with a subscription
Features
-
Simple online access to standards, technical information and regulations.
-
Critical updates of standards and customisable alerts and notifications.
-
Multi-user online standards collection: secure, flexible and cost effective.