UNE-EN 15882-2:2016
Superseded
A superseded Standard is one, which is fully replaced by another Standard, which is a new edition of the same Standard.
Extended application of results from fire resistance tests for service installations - Part 2: Fire dampers
Hardcopy , PDF
Spanish, Castilian, English
28-09-2016
15-02-2023
This European Standard provides guidance and rules to notified bodies (for Fire Dampers) to allow them to produce/validate an extended field of application report for fire dampers. This standard identifies the parameters that affect the fire resistance of dampers. It also identifies the factors that need to be considered when deciding whether, or by how much, the parameter can be extended when contemplating the fire resistance performance of an untested, or untestable variation in the construction.
This European Standard explains the principles behind how a conclusion on the influence of specific parameters/constructional details relating to the relevant criteria (E,I,S) can be achieved.
This European Standard does not cover dampers used for smoke control.
This European Standard only applies to extended fields of application based on tests successfully undertaken to EN 1366-2. Only test reports that have a total test time where the criteria are fulfilled that is in excess of the required classification period by a margin of either 10 % or 12 minutes, whichever is the least, are to be considered. Each classification (E,I,S) is to be considered individually consequently E (134 minutes achieved) may be extended, but EI (61 minutes achieved) may not be extended.
Additionally, leakage determined during such tests is to be at least 10 % below the leakage limits for E, or for ES, dependent on classification achieved, given in EN 13501-3 before the EXAP rules can be applied. The 10 % below the leakage limits is to be fulfilled for the extended period in addition to the classification period.
By application of this European Standard, it should be possible to identify what specifications should be tested to maximize the field of application. Some information on test programmes is given for guidance purposes.
| Committee |
CTN 23
|
| DocumentType |
Standard
|
| Pages |
26
|
| PublisherName |
Asociación Española de Normalización
|
| Status |
Superseded
|
| Standards | Relationship |
| EN 15882-2:2015 | Identical |
| EN 15882-1:2011+A1:2017 | Extended application of results from fire resistance tests for service installations - Part 1: Ducts |
| EN 1366-1:2014 | Fire resistance tests for service installations - Part 1: Ventilation ducts |
| EN 13501-3:2005+A1:2009 | Fire classification of construction products and building elements - Part 3: Classification using data from fire resistance tests on products and elements used in building service installations: fire resisting ducts and fire dampers |
| EN 1363-1:2012 | Fire resistance tests - Part 1: General Requirements |
| EN 1366-2:2015 | Fire resistance tests for service installations - Part 2: Fire dampers |
| ISO 10294-4:2001 | Fire resistance tests — Fire dampers for air distribution systems — Part 4: Test of thermal release mechanism |
| ISO 10294-1:1996 | Fire resistance tests — Fire dampers for air distribution systems — Part 1: Test method |