Customer Support: 131 242

  • There are no items in your cart
We noticed you’re not on the correct regional site. Switch to our AMERICAS site for the best experience.
Dismiss alert

ASTM D 6450 : 2005

Superseded

Superseded

A superseded Standard is one, which is fully replaced by another Standard, which is a new edition of the same Standard.

View Superseded by

Standard Test Method for Flash Point by Continuously Closed Cup (CCCFP) Tester

Available format(s)

Hardcopy , PDF

Superseded date

11-11-2014

Language(s)

English

Published date

01-05-2005

$122.77
Including GST where applicable

Committee
D 02
DocumentType
Test Method
Pages
7
ProductNote
Reconfirmed 2005
PublisherName
American Society for Testing and Materials
Status
Superseded
SupersededBy
Supersedes

1.1 This flash point test method is a dynamic method and depends on definite rates of temperature increase. It is one of the many flash point test methods available, and every flash point test method, including this one, is an empirical method.

Note 1

Flash point values are not a constant physical-chemical property of materials tested. They are a function of the apparatus design, the condition of the apparatus used, and the operational procedure carried out. Flash point can therefore only be defined in terms of a standard test method, and no general valid correlation can be guaranteed between results obtained by different test methods or with test apparatus different from that specified.

1.2 This test method covers the determination of the flash point of fuel oils, lube oils, solvents, and other liquids by a continuously closed cup tester. The measurement is made on a test specimen of 1 mL.

1.3 This test method utilizes a closed but unsealed cup with air injected into the test chamber.

1.4 This test method is suitable for testing samples with a flash point from 10 to 250C.

Note 2

Flash point determinations below 10°C and above 250°C can be performed; however, the precision has not been determined below and above these temperatures.

1.5 If the user's specification requires a defined flash point method other than this test method, neither this test method nor any other method should be substituted for the prescribed method without obtaining comparative data and an agreement from the specifier.

1.6 The values stated in SI units are to be regarded as the standard. The values given in parentheses are for information only. Temperatures are in degree Celsius, and pressure is in kilo-pascals.

1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. Specific warning statements appear throughout the standard.

ASTM F 3337 : 2019 Standard Guide for Taking Property and Behavior Measurements on Weathered Fractions of Oil
ASTM D 7094 : 2017 : REV A Standard Test Method for Flash Point by Modified Continuously Closed Cup (MCCCFP) Tester
ASTM D 6823 : 2008 : R2013 Standard Specification for Commercial Boiler Fuels With Used Lubricating Oils
ASTM D 6448 : 2016 Standard Specification for Industrial Burner Fuels from Used Lubricating Oils
ASTM D 6751 : 2019 Standard Specification for Biodiesel Fuel Blend Stock (B100) for Middle Distillate Fuels

Access your standards online with a subscription

Features

  • Simple online access to standards, technical information and regulations.

  • Critical updates of standards and customisable alerts and notifications.

  • Multi-user online standards collection: secure, flexible and cost effective.

Need help?
Call us on 131 242, then click here to start a Screen Sharing session
so we can help right away! Learn more